Fire damper testing and inspections

Fire damper maintenance: what happens after a failed test

A failed damper is not the end of the job. It is the start of one.

Facilities managers, building owners and fire risk assessors: who fixes a failed damper, how the retest is recorded, and how anyone can later prove it was put right.

Edward Bristow17 December 20264 min read

Most fire damper paperwork is built around the test. The harder question for a building owner is what happens next: who fixes the damper, how quickly, and how anyone can later prove it was put right.

What the law asks

In England and Wales, Article 17 of the Regulatory Reform (Fire Safety) Order 2005 asks the responsible person to keep fire safety equipment under a suitable system of maintenance, "in an efficient state, in efficient working order and in good repair". Fire dampers sit inside that duty. Scotland (Fire Safety (Scotland) Regulations 2006, regulation 16) and Northern Ireland (Fire Safety Regulations (Northern Ireland) 2010, regulation 16) carry the same maintenance wording.

The law does not stop at "tested". A damper that failed and was never repaired is not in good repair, whatever the test certificate says.

How often, and by whom

BESA's guidance says dampers should be tested by a competent person on completion and at least annually after that, following BS 9999, with "competent person" as defined by BESA's DW145 guide. BESA also asks for accurate, verifiable records and a full asset register showing the condition and location of each damper (BESA, 24 June 2026).

What the test report should already tell you

BESA's December 2025 guide lists what a damper report should hold, including pass or fail results, details of what was wrong, and recommended corrective actions with timescales (BESA, 19 December 2025). That last line is the start of maintenance. If your report lists failures but no action and no date, ask your contractor for both.

Maintenance is damper by damper

A site may have hundreds of dampers. If twelve fail, the work that follows is about those twelve:

  1. The remedial - what is wrong with each failed damper and what will be done (repair, replace, or a part such as a fusible link).
  2. The retest - each repaired damper is tested again. Only the dampers retested should change status; the rest keep the results and due dates they already had.
  3. The record - each damper's history shows the failed test, the remedial and the passing retest, so the answer to "was it fixed?" sits against that damper's reference and location.

Where this breaks down is when the retest is written up as a fresh site visit. The register then shows a "new" test for the whole building, and the link between the failure and the fix is lost.

Inspections between tests

A visual inspection between annual tests can catch a damper that has been damaged, blocked or disconnected since it last passed. It is a reason to bring a test forward. It is not a test, and it does not clear one.

Smoke dampers too

Smoke dampers and combined fire and smoke dampers follow the same pattern: tested, recorded, put right when they fail, and retested. Keep them in the same register, marked by type.

Questions for your contractor

  • Does every failed damper on the report carry a recommended action and a timescale?
  • Will the retest cover only the failed dampers, with each one's result recorded against its own reference?
  • After the retest, can you see one damper's whole history - fail, remedial, pass - on one record?
  • Does each damper keep its own next due date?

How SMART Reports records it

In SMART Reports a failed damper gets a retest that moves only the dampers retested; every other damper keeps its own due date. The certificate is marked Satisfactory or Unsatisfactory, with a test report and a location plan with damper dots. Inspections are included between tests: an inspection can bring a test forward, never clears one, and no certificate follows it. See how it works on our fire damper testing software page, or run "Retest a failed fire damper" in the live demo.

General information, not legal advice. The duty sits with the responsible person for the building.